Electrical connection SMA America, LLC
58 SB30-40US-IUS103030 Installation Guide
Jumper configuration for RS485 communication
RS485 pinouts
2 - A (+) (Data+)
7 - B ( ) (Data )
5 - SR (Signal Ref.)
Jumpers B and C Installed: Installing these jumpers puts 680 Ohm symmetry resistors between
pin 2 (Data+) and +5V and between pin 7 (Data ) and Ground.
Jumper A installed: Installing this jumper puts a 120 Ohm termination resistor across
pin 2 (Data+)and pin 7 (Data ).
Install jumper A only, if the inverter is on one of the ends of the RS485 bus.
Install jumpers B and C only:
After the inverter is on the RS485 bus.
Only if symmetry of the signal is required.
Symmetry is already provided by the Sunny Boy Control and Sunny WebBox products.
RS485 Piggy-Back
Communication Module
Signal Symmetry and
Termination Jumpers
Terminal Block for
RS-485 Connection