Displays and messages SMA America, LLC
76 SB30-40US-IUS103030 Installation Guide
Fixed operating parameters
V-Const Setval V SB 3000‑US:
185 ... 500
SB 3800‑US:
230 … 600
SB 4000‑US:
230 ... 600
SB 3000‑US:
500
SB 3800‑US:
600
SB 4000‑US:
600
Installer PV Setpoint voltage for constant
voltage operation. These
parameters only are important in
case the parameter “Operating
Mode“ is set to “V-const“.
Vac-Min* % 0 ... 50 12 Installer Values are used to calculate the
lower limit of allowable AC voltage.
Default value is optimal for
installations < 30 kW. The default
12 results in a trip value of 88 % as
listed under trip limits.
Vac-Max* % 0 ... 20 10 Installer Values are used to calculate the
upper limit of allowable AC voltage.
Default value is optimal for
installations < 30 kW. The default
10 results in a trip value of 110 % as
listed under trip limits.
Vac-Min-Fast* % 0 ... 50 50 Installer Values are used to calculate the
lower limit of allowable AC voltage
for fast disconnection. Default value
is optimal for installations < 30 kW.
The default 50 results in a trip value
of 50 % as listed under trip limits.
Vac-Max-Fast* % 0 ... 20 20 Installer Values are used to calculate the
upper limit of allowable AC voltage
for fast disconnection. Default value
is optimal for installations < 30 kW.
The default 20 results in a trip value
of 120 % as listed under trip limits.
Vac-Min-Recnet % 0 ... 50 11.7 Installer Values are used to calculate the
lower and upper limits to reconnect
to the grid after a grid frailure.
Vac-Max-Recnet % 0 ... 20 5.83 Installer
Vpv-Start V SB 3000‑US:
166 ... 480
SB3800‑US:
208 ... 580
SB 4000‑US:
208 ... 580
SB3000‑US:
228
SB3800‑US:
285
SB4000‑US:
285
Installer Minimum DC voltage for the Sunny
Boy to connect to the grid.
Name Unit Range Default Description
Plimit W fixed SB3000‑US: 3050
SB3800‑US: 4050
SB4000‑US: 4050
Upper limit of AC output power
SMA-SN Serial Number of the Sunny Boy
Software-BFR Firmware version of the operation
control unit (BFR)
Software-SRR Firmware version of the current
control unit (SRR)
Name Unit Range Default Password
Level
Description