11 Operating Data and Parameters
SMA Solar Technology AG
User Manual 115SCCPXT-E7-BA-en-58
11 Operating Data and Parameters
11.1 Operating Data
11.1.1 Inverter
11.1.1.1 Power Limitation
Errors and warnings relating to active power limitation
Name Display Description
P-WModFailStt Off No mode for active power limitation has been selected.
Ok A mode for active power limitation has been selected and no error is
present.
ComFail
The mode WCtlCom has been selected and the expected signal with
a valid active power limitation has been absent for at least fivemin-
utes.
AnInFail
The mode WCnstNomAnIn has been selected and the value mea-
sured at the analog input is less than 2mA.
ComInvalid
The mode WCtlCom has been selected and there is invalid content
in the power setpoint information.
Status messages of active power limitation
Name Display Description
P-WModStt Off No mode for active power limitation has been selected.
WMax Active power is limited by specification of an upper limit. This limit is
based on Pmax.
Hz Active power is limited by a frequency increase.
Tmp Active power is limited by temperature derating.
AmpPv Active power is limited via a PV current limitation.
AmpAC Active power is limited via an AC current limitation.
SMax The active power is limited by the maximum apparent power.
Q-VAr The active power is limited due to the priority of the reactive power
setpoint.
QEnsure The active power is limited due to the intermediate storage of reac-
tive power.
P-Vtg The active power is limited due to the characteristic curve P(V).
VdcMax The active power is increased via the setpoint due to the DC voltage
being too high.
AmpPvOptiprot For the order option "Optiprotect", the active power is limited due to
switch currents being too high.