11 Operating Data and Parameters
SMA Solar Technology AG
User Manual 121SCCPXT-E7-BA-en-58
11.2 Parameters
11.2.1 Inverter
11.2.1.1 Power Limitation
Name Description Value/range Explanation Default
value
Plimit* Limitation of the nominal
device power including
apparent power
0kW to 550kW SunnyCentral500CPXT 550kW
0kW to 700kW SunnyCentral630CPXT 700kW
0kW to 792kW SunnyCentral720CPXT 792kW
0kW to 836kW SunnyCentral760CPXT 836kW
0kW to 880kW SunnyCentral800CPXT 880kW
0kW to 935kW SunnyCentral850CPXT 935kW
0kW to 990kW SunnyCentral900CPXT 990kW
0kW to 1100kW SunnyCentral1000CPXT 1,100kW
Pmax** Limitation of the nominal
power
0kW to 550kW SunnyCentral500CPXT 550kW
0kW to 700kW SunnyCentral630CPXT 700kW
0kW to 792kW SunnyCentral720CPXT 792kW
0kW to 836kW SunnyCentral760CPXT 836kW
0kW to 880kW SunnyCentral800CPXT 880kW
0kW to 935kW SunnyCentral850CPXT 935kW
0kW to 990kW SunnyCentral900CPXT 990kW
0kW to 1100kW SunnyCentral1000CPXT 1,100kW
P-WMod** Mode for active power
limitation
Off
Limits active power to Pmax
Off
WCtlCom Limits active power via an exter-
nal control unit, such as the
Power Reducer Box
WCnst Manually limits active power in
kW (P-W) via communication de-
vices, such as the SC-COM
WCnstNom Manually limits active power in%
(P-WNom) via communication
devices, such as the SC-COM
WCnstNomAnIn Limits active power in% at the
analog input
WCnstNomDigIn Limits active power at the digital
input. This mode is not supported.