EasyManua.ls Logo

SMA SUNNY CENTRAL CP XT Series - Sunny String-Monitor

SMA SUNNY CENTRAL CP XT Series
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 Operating Data and Parameters
SMA Solar Technology AG
User ManualSCCPXT-E7-BA-en-58142
Name Description Value/range Explanation Default
value
DevFunc* Manages the Sunny String-Moni-
tors
AutoDetect_
SSMU
Searches for all SunnyString-
Monitors and deletes previ-
ously detected SunnyString-
Monitors
0
DetectSSMU
Retry
Searches for undetected
SunnyString-Monitors only
DelAll_SSMU Deletes all detected
SunnyString-Monitors
Factory Resets all parameters to default
settings.
* To change these parameters, you must enter the installer password.
11.2.3 Sunny String-Monitor
Name Description Value/range Explanation Default
value
TMittelung* Duration of averaging of current
measurements
0sto6,000s 30s
String Anzahl* Number of detected strings 0 to 8 0
SW Version Current firmware version 1 to 40 Value cannot be changed
SSM Identifier* Identification number of Sunny
String-Monitor
1 to 99 0
Group String
1*
Assigns strings to their respective
group
0 to 3 Parameter exists for all eight
groups
0
Group String* All groups 0 to 3 0
No.of String 1* Number of connected strings in
the respective group
1 to 4 Parameter exists for all eight
groups
If you wish to use this function,
contact us (see Section13,
page153).
No.of Strings* All groups 1 to 4
Monitoring1
On*
Start of monitoring of strings in
group 1
0:00 a.m. to
11:59 p.m.
Parameter exists for all eight
groups
Configure the string settings
preferably via the SunnyCen-
tralString-MonitorController.
0
Monitoring1
Off*
End of monitoring of strings in
group 1
0:00 a.m. to
11:59 p.m.
Parameter exists for all eight
groups
Configure the string settings
preferably via the SunnyCen-
tralString-MonitorController.
0

Table of Contents

Other manuals for SMA SUNNY CENTRAL CP XT Series

Related product manuals