11 Operating Data and Parameters
SMA Solar Technology AG
User Manual 133SCCPXT-E7-BA-en-58
Name Description Value/range Explanation Default
value
QoDDccOffDe-
lay*
Delay time until the DC
switchgear opens in the
operating state
"QatNight"
0s … 86,400s ‒ 3,600s
* You can only view this parameter.
** To change this parameter, you must enter the installer password.
*** To view or change this parameter, you must enter the installer password.
11.2.1.2 Grid Monitoring and Grid Limits
To change these parameters, you must enter the installer password.
Name Description Range Explanation Default
value
VRtg Nominal line-to-line volt-
age of the utility grid
1V to 70,000V ‒ 20,000 V
VCtlMax Threshold for overvolt-
age release level3
100% ... 150% ‒ Country-
specific
VCtlMaxTm Delay time for overvolt-
age level3
0 ms …
1,000,000ms
‒ Country-
specific
VCtlhhLim Threshold for overvolt-
age release level2
100% ... 150% ‒ Country-
specific
VCtlhhLimTm Delay time for overvolt-
age level2
0 ms …
1,000,000ms
‒ Country-
specific
VCtlhLim Threshold for overvolt-
age release level1
100% ... 150% ‒ Country-
specific
VCtlhLimTm Delay time for overvolt-
age level1
0 ms …
1,000,000ms
‒ Country-
specific
VCtllLim Threshold for undervolt-
age release level1
0% ... 100% ‒ Country-
specific
VCtllLimTm Delay time for undervolt-
age level1
0 ms …
1,000,000ms
‒ Country-
specific
VCtlllLim Threshold for undervolt-
age release level2
0% ... 100% ‒ Country-
specific
VCtlllLimTm Delay time for undervolt-
age level2
0 ms …
1,000,000ms
‒ Country-
specific
VCtlMin Threshold for undervolt-
age release level3
0% ... 100% ‒ Country-
specific
VCtlMinTm Delay time for undervolt-
age level3
0 ms …
1,000,000ms
‒ Country-
specific