7 Troubleshooting
SMA Solar Technology AG
User Manual 67SCCPXT-E7-BA-en-58
7.5.2 Explanation of the Error Tables
You will find the following information in the error tables in the following sections:
1301
3803
0104
Error no.
Grid voltage is too high.
DC current of PV array is too high.
Left-hand rotating magnetic field
is connected.
Explanation
W
1 min
30 s
S1
C
D
Q
S2
x
R Corrective measures
• Check phase position.
• Check DC input current.
• Check grid voltage.
A B
Position Explanation
A Behavior of the inverter: disturbance levelS1, disturbance levelS2
s / min: waiting time
C: system-specific
D: day change
Q: waiting for acknowledgement
W: warning
B Reset
7.5.3 Error Numbers 01xx to 13xx - Disturbance on the Utility Grid
After a grid failure, the inverter monitors the utility grid for a specific period before reconnecting. When the inverter
monitors the utility grid after a grid error, the grid monitoring time is complied with. Certain errors, such as grid errors,
cause the inverter to shut down. In this case, the instantaneous value TmsRmg indicates the time for which the inverter
monitors the utility grid before reconnecting. This grid monitoring time can be defined in parameter GdErrTm.
Error no. Explanation Inverter behavior Corrective measures
S1 S2 R
0103* Grid voltage is too high. Overvolt-
age detected by redundant moni-
toring.
30s 30s Check the grid voltage.
Check grid connections.
Check stability of the utility grid.
Make sure the external fuses work
properly.
Make sure the AC cable connections
are tight.
0104* Grid voltage is too high. Overvolt-
age detected by standard monitor-
ing.
C C
0203* Grid voltage is too low. Undervolt-
age detected by redundant moni-
toring.
30s 30s
0204* Grid voltage is too low. Undervolt-
age detected by standard monitor-
ing.
30s 30s
0205* Not permitted grid frequency
change or grid synchronization
not possible
30s 30s