7 Troubleshooting
SMA Solar Technology AG
User ManualSCCPXT-E7-BA-en-5864
7.3 Reading Off Disturbance Messages
7.3.1 Reading Off Error Messages via Touch Display
If an error occurs, a warning symbol is shown on the touch display.
Procedure:
• Select the warning symbol.
☑ The touch display lists the error number, waiting time, error message and the necessary corrective measure to
eliminate the disturbance.
7.3.2 Reading Off Disturbance Messages via the User Interface
1. Log into the user interface (see Section9.4.1, page78).
2. To display the error number, select the instantaneous value ErrNo in the instantaneous value view.
3. To display the delay time, select the instantaneous value TmsRmg in the instantaneous value view.
4. To display the error message, select the instantaneous value Msg in the instantaneous value view.
5. To display the corrective measure, select the instantaneous value Dsc in the instantaneous value view.
7.3.3 Displaying the Event Report
7.3.3.1 Enabling Automatic Read-Out of Events
1. Log into the user interface (see Section9.4.1, page78).
2. Select SunnyCentral > Recording.
3. In the field Collect automatically fault logs, select yes.
4. Select the button [Save].
7.3.3.2 Displaying and Downloading the Event Report
The event report keeps a log of various events, e.g. errors and warnings. All events can be downloaded in a CSV file.
Upon delivery, the automatic transfer of the events is deactivated.
Procedure:
1. Log into the user interface (see Section9.4.1, page78).
2. In order to have the event report of the inverter displayed manually, proceed as follows:
• Select SunnyCentral > Recording.
• In the field Manually requesting fault memory, select [Request].
• In the field Manually requesting event memory, select [Request].
3. Select SunnyCentral > Events.
4. To download the events as CSV file, carry out the following steps:
• Select the button [Download].
• Choose the save location.
• Select the button [Save].