11 Operating Data and Parameters
SMA Solar Technology AG
User Manual 141SCCPXT-E7-BA-en-58
Name Description Value/range Explanation Default
value
Tm Entry of current time 0 to 235959 Entered in the format HH-
MMSS
‒
TolGr1* Deviation of group1 currents
from mean value
5% to 100% Parameter exists for all six
groups.
13%
MoniTm-
Gr1On*
Start time for monitoring of
group1
07:00 a.m. to
7:00 p.m.
Parameter exists for all six
groups.
10:00 a.m.
MoniTm-
Gr1Off*
End time for monitoring of
group1
07:00 a.m. to
7:00 p.m.
Parameter exists for all six
groups.
3:00 p.m.
MoniTmGrAl-
lOn*
Start time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒ 10:00 a.m.
MoniTm-
GrAllOff*
End time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒ 3:00 p.m.
MoniTm-
ComOn*
Start time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒ 10:00 a.m.
MoniTmCo-
mOff*
End time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒ 3:00 p.m.
Ackn Acknowledge errors quit ‒ ‒
ErrLevGr1* Sensitivity of error detection for
group1
Parameter exists for all six groups
24 Sensitive 50 min ‒ 10% 32 Regular
24 Regular 50 min ‒ 14%
24 Insensitive 50 min ‒ 18%
32 Sensitive 35 min ‒ 10%
32 Regular 35 min ‒ 13%
32 Insensitive 35 min ‒ 16%
64 Sensitive 15 min ‒ 7%
64 Regular 15 min ‒ 9%
64 Insensitive 15 min ‒ 10%
ComBaud* Baud rate 1,200 baud Parameter can only be
changed in the operating state
"Stop".
19,200
baud
4,800 baud
9,600 baud
19,200 baud
38,400 baud
57,600 baud