11 Operating Data and Parameters
SMA Solar Technology AG
User Manual 129SCCPXT-E7-BA-en-58
Name Description Value/range Explanation Default
value
WGraReco-
nEna**
Activation of the decou-
pling protection ramp for
reconnection
Off Deactivated Country-
specific
On Activated
P-VtgGra-
Nom**
Active power gradient
for voltage-dependent
active power limitation
0.017%/s to
100.000%/s
‒ 0.166%/s
P-VtgEna Activation of voltage-de-
pendent active power
limitation
Off Deactivated Off
On Activated
P-VtgNomP1 Voltage at point1 100% … 120% ‒ 111%
P-VtgNomP2 Voltage at point2 90% … 120% ‒ 110%
P-VtgAtMin Minimum active power
with voltage-dependent
active power limitation
0% … 100% ‒ 20%
PwrApLimit-
Prio***
Prioritization of reactive
power or active power
PrioPwrRtPrioPwrRt Prioritization of reactive power PrioPwrRtPri-
oPwrRt
PrioPwrAt Prioritization of active power
SDLimCom-
Src***
Selection of the SDLimit
source
CAN Interface of the communication
unit
UART
UART Via SMA Net
P-WSubVal Substitute value for ac-
tive power limitation out-
side of normal feed-in
operation during commu-
nication disturbance
0kW to 550kW SunnyCentral500CPXT 550kW
0kW to 700kW SunnyCentral630CPXT 700kW
0kW to 792kW SunnyCentral720CPXT 792kW
0kW to 836kW SunnyCentral760CPXT 836kW
0kW to 880kW SunnyCentral800CPXT 880kW
0kW to 935kW SunnyCentral850CPXT 935kW
0kW to 990kW SunnyCentral900CPXT 990kW
0kW to 1100kW SunnyCentral1000CPXT 1,100kW