7 Troubleshooting
SMA Solar Technology AG
User Manual 69SCCPXT-E7-BA-en-58
Error no. Explanation Inverter behavior Corrective measures
S1 S2 R
3501 The insulation monitoring device
has measured a too low ground-
ing resistance.
C C Check the PV array for ground faults.
3502 The GFDI has tripped. C C Check the PV array for ground faults.
3504 The insulation monitoring device
has detected an insulation error.
If the parameter IsoErrIgn is set to
On, this error is ignored.
W W Check the PV array for ground faults.
3507 A ground fault has occurred on
the ungrounded terminal of the PV
array.
Q Q Check the PV array for ground faults.
3510 The inverter has detected an insu-
lation error on the inverter bridge.
Q Q Check the PV array for ground faults.
3511 The inverter has detected an insu-
lation error.
W W Check the PV array for ground faults.
3512 The RemoteGFDI has detected a
permanent ground fault.
Q Q Check the PV array for ground faults.
3515 A ground fault detected by
SoftGrounding has been ignored.
W W Check the PV array for ground faults.
3517 Insulation measuring is being per-
formed.
W W
3520 An insulation fault has occurred
and has been fixed.
W W
3601 Leakage current to ground has oc-
curred in the PV array or the
threshold defined in parameter
RisoCtlWarn has been reached.
W W Check the grounding and equipotential
bonding.
Check the module wiring and system
design.
Check the parameter RisoCtlWarn.
3803 The PV array current is too high. 1 min D Check the DC input current.
Check the module wiring and system
design.
4003 Reverse currents detected in the PV
array or DC connection polarity
reversed.
30s Q Check the PV modules for short circuits.
Check the module wiring and system
design.
Check the DC terminals for correct
polarity.
Check the functionality of the entire
string.