Parameter lists SMA America, LLC
160 SI5048U-TUS121440 Technical Description
19.2.2 Battery Settings (220#)
#221 Battery Property
No. Name Description Value Explanation Default
value
01 BatTyp Battery type VRLA Valve regulated lead
acid (AGM or GEL
type)
VRLA
FLA Flooded lead acid
battery
NiCd Nickel-cadmium
battery
02 BatCpyNom Nominal battery
capacity
(E:C10/U:C20)
100 Ah
03 BatVtgNom Nominal battery
voltage
VRLA 48 V
FLA 48 V
NiCd 45.6 V
04 BatTmpMax Maximum battery
temperature
104°F … 122°F
(40 °C … 50 °C)
113°F
(45 °C)
05 BatTmpStr Battery start
temperature
following stop due
to overtemperature
32 °F ... 104 ° F
(0 °C … 40 °C)
”BatTmpMax”
104°F
(40 °C)
06 BatWirRes Power resistor of
the battery
connection in
mOhm
0mOhm…
50 mOhm
07 BatFanTmpStr Starting
temperature for the
”BatFan” function
104°F
(40 °C)