Electrical Connection SMA America, LLC
54 SI5048U-TUS121440 Technical Description
5. Connect the Sunny Island master to the slave.
Number of slaves Connection Procedure
1 slave Take the RJ45 cable leading away from the master, introduce
it into the Sunny Island slave and plug it into the ”ComSyncIn
socket.
Leave the termination resistor plugged into the ”ComSyncOut”
socket.
The Sunny Island master and slave are connected.
2 slaves Take the RJ45 cable leading away from the master, introduce
it into the Sunny Island slave 1 and plug it into the
”ComSyncIn” socket there.
Remove the terminating resistor from theComSyncOut socket
in the Sunny Island slave 1.
Plug the RJ45 cable included in delivery into the
”ComSyncOut” socket of the slave 1.
Take the RJ45 cable leading away from the slave 1, introduce
it into the Sunny Island slave 2 and plug it into the
”ComSyncIn” socket there.
The Sunny Island master and the slaves are connected.
Master Slave 1 Slave 2
termination
resistor
location
termination
resistor
location