HGM400 Series Genset Controller User Manual
HGM400 Series Genset Controller ISSUE 2015-05-27 Version 1.6 Page 14 of 44
3
Gen Over
Current
When the controller detects that the genset current has
exceeded the pre-set value and the over current delay has
expired, it will initiate a warning alarm and the corresponding
alarm information will be displayed on LCD.
4
Fail To Stop
After “fail to stop” delay/ ETS delay has expired, if gen-set
does not stop completely, it will initiate a warning alarm and
the corresponding alarm information will be displayed on
LCD.
5
Low Fuel Level
When the controller detects that the fuel level has fallen
below the pre-set value while shutdown is prohibited, or
detects that the Aux. input low fuel level while shutdown is
prohibited, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
6
Charge Alt
Failure
When the controller detects that charger voltage has fallen
below the pre-set value, it will initiate a warning alarm and
the corresponding alarm information will be displayed on
LCD.
7
Battery Under
Volt
When the controller detects that battery voltage has fallen
below the pre-set value, it will initiate a warning alarm and
the corresponding alarm information will be displayed on
LCD.
8
Battery Over
Volt
When the controller detects that battery voltage has
exceeded the pre-set value, it will initiate a warning alarm
and the corresponding alarm information will be displayed on
LCD.
9
Auxiliary Input
When the controller detects that the auxiliary input warning
signals, it will initiate a warning alarm and the corresponding
alarm information will be displayed on LCD.
10
Loss Of Speed
Signal
When the controller detects that the engine speed is 0 and
the delay is 0, it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
11
Low Coolant
Level
When the controller detects the low coolant level input is
active, it will initiate a warning alarm and the corresponding
alarm information will be displayed on LCD.
12
Temp. Sensor
Open
When the controller detects that the temperature sensor is
open circuit and the action select Warn”, it will initiate a
warning alarm and the corresponding alarm information will
be displayed on LCD.
13
Oil Pressure
Sensor Open
When the controller detects that the oil pressure sensor is
open circuit and the action select Warn”, it will initiate a
warning alarm and the corresponding alarm information will
be displayed on LCD.