HGM400 Series Genset Controller User Manual
HGM400 Series Genset Controller ISSUE 2015-05-27 Version 1.6 Page 17 of 44
No
Items
Description
LCD.
5
Under Speed
When the controller detects that the generator speed has
fallen below the pre-set value, it will initiate a shutdown alarm
and the corresponding alarm information will be displayed on
LCD.
6
Loss Of Speed
Signal
When the controller detects that the engine speed is 0 and
the delay is NOT 0, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.
7
Gen Over
Voltage
When the controller detects that the genset voltage has
exceeded the pre-set value, it will initiate a shutdown alarm
and the corresponding alarm information will be displayed on
LCD.
8
Gen Under
Voltage
When the controller detects that the genset voltage has
fallen below the pre-set value, it will initiate a shutdown alarm
and the corresponding alarm information will be displayed on
LCD.
9
Gen Over
Current
When the controller detects that the genset current has
exceeded the pre-set value and delay is not 0, it will initiate a
shutdown alarm and the corresponding alarm information will
be displayed on LCD.
10
Fail To Start
If the engine does not fire after the pre-set number of
attempts, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.
11
Gen Over
Frequency
When the controller detects that the genset frequency has
exceeded the pre-set value, it will initiate a shutdown alarm
and the corresponding alarm information will be displayed on
LCD.
12
Gen Under
Frequency
When the controller detects that the genset frequency has
fallen below the pre-set value, it will initiate a shutdown alarm
and the corresponding alarm information will be displayed on
LCD.
13
No Gens
Frequency
When the controller detects that the genset frequency is 0, it
will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
14
Low Fuel Level
When the controller detects that the fuel level has fallen
below the pre-set value or detects that the low fuel level input
is active, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.
15
Low Coolant
Level
When the controller detects the low coolant level input is
active, it will initiate a shutdown alarm and the corresponding
alarm information will be displayed on LCD.
16
Temp. Sensor
When the controller detects that the temperature sensor is