HGM400 Series Genset Controller User Manual
HGM400 Series Genset Controller ISSUE 2015-05-27 Version 1.6 Page 18 of 44
open circuit and the action select “Shutdown”, it will initiate a
shutdown alarm and the corresponding alarm information will
be displayed on LCD.
When the controller detects that the oil pressure sensor is
open circuit and the action select “Shutdown”, it will initiate a
shutdown alarm and the corresponding alarm information will
be displayed on LCD.
When the controller detects that the level sensor is open
circuit and the action select “Shutdown”, it will initiate a
shutdown alarm and the corresponding alarm information will
be displayed on LCD.
If the config. sensor set as temperature sensor, When the
controller detects that the temperature sensor is open circuit
and the action select “Shutdown”, it will initiate a shutdown
alarm and the corresponding alarm information will be
displayed on LCD.
Oil Pressure
Sensor 2 Open
If the config. sensor set as oil pressure sensor, When the
controller detects that the oil pressure sensor is open circuit
and the action select “Shutdown”, it will initiate a shutdown
alarm and the corresponding alarm information will be
displayed on LCD.
If the config. sensor set as level sensor, When the controller
detects that the level sensor is open circuit and the action
select “Shutdown”, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that config. sensor temperature
(sensor type: temperature sensor) has exceeded the pre-set
value, it will initiate a shutdown alarm and the corresponding
alarm information will be displayed on LCD.
When the controller detects that config. sensor oil pressure
(sensor type: oil pressure sensor) has fallen below the
pre-set value, it will initiate a shutdown alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that config. sensor fuel level
(sensor type: level sensor) has fallen below the pre-set
value, it will initiate a shutdown alarm and the corresponding
alarm information will be displayed on LCD.
When genset running time has exceeded the user setting
maintenance time and the action select “Shutdown”, it will
initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD. The maintenance
alarm will reset if the action select “Inactive”.