ATYSp - 542001E - SOCOMEC
1
SETUP
Definition AdjustmentRange M-G M-M
CT SEC 5
Current Transformer secondary rating 1A
2A
• •
S1=SW2 NO
Inverted power section switch wiring. Switch
1 (Front) cabled as Switch 2 and Switch 2
(Back) cabled as Switch 1.
NO: Not Inverted
YES: Inverted
NO
YES
• •
BACKLGHT INT
The LCD backlight may be set to:
OFF: Always Off
ON: Always On
INT: On after pressing the keypad and during
operating sequences only. (Turned off after 2
minutes of inactivity).
OFF
ON
INT
• •
CODE P 1000
Password Code to modify and save settings
in Programming Mode.
Default factory setting: 1000
0000 to 9999 • •
CODE E 0000
Password Code to modify and save settings
in Operating Mode.
Default factory setting: 0000
0000 to 9999 • •
BACKUP SAVE
Save the settings in the backup so as to recall
them later within the same menu.
Load to charge the backup data
SAVE
LOAD
• •
AnnexeI-6.1.**Phaserotationcheck:
This functionality checks the consistency of phase rotation i.e. of the wiring prior to commissioning.
Example: If the parameter ROT PH = ABC:
L1 (A)
L2 (B)L3 (C)
OK
L1 (A)
L3 (C)L2 (B)
NON OK
Display
12
or
12
depending on the non-compliant source
(Rotation check on sources
1
and
2
).
WARNING
Function available on both sources in case of 4NBL/4BL or 3NBL/3BL type of
network and only on source
1
in case of 41NBL or 42NBL network.