24 SOCOMEC - Ref. : 875 092A
Address
Totalizing meters
METERS DISPLAY
Pulse meters for power demand storing
Decimal Hexadecimal N° of words (1) Description Unity
768 300 2 Meter 1
770 302 2 Meter 2
772 304 2 Meter 3
774 306 2 Meter 4 in energy metering
776 308 2 Meter 5
778 30A 2 Meter 6
780 30C 2 Meter 7
782 30E 2 Value between 2 signals for input 1 Pulses
784 310 2 Value between 2 signals for input 2
786 312 2 Value between 2 signals for input 3
788 314 2 Value between 2 signals for input 4
Zone size (1): 22 words in decimal or 16 in hexadecimal.
0.01 kWh
and no value in pulses
DISPLAY (FUNCTION 3)
METERS
NB:
A maximum of 60 words can be read
in one frame.
COMMUNICATION
The Countis Ci system communicates via a JBUS/MODBUS
®
protocol invol-
ving a master/slave dialogue. Two dialogues are possible:
the master communicates with a slave (Countis Ci) and waits for its response,
the master communicates with all the slaves (Countis Ci) without waiting for
their response.
The communication mode is the RTU mode (Remote Terminal Unit) with
hexadecimal characters consisting of 8 bits.
NB:
The integration time must not exceed
3 silences (the time taken to transmit
a character) for the message to be
processed.
By selecting slave address 0, the
same message is transmitted to all
the Countis devices present on the
network (only for functions 6 and 16).
COMMUNICATION FORMAT
Slave address Function code Address Data CRC16
3 to read n words (128 maximum )
6 to write a word
8 to diagnose master/slave exchanges from meters 1, 3, 4, 5 and 6
16 to write n words (128 maximum)
This is a standard format consisting of:
The following functions are essential in order to make full use of information: