13
COUNTIS ECi - Ref.: 538 470 A
TECHNICAL CHARACTERISTICS
This symbol indicates that the product may not be disposed of with other
household waste, so as not to harm the environment or human health
(WEEE directive, 2002/96/EC). Please refer to the standard terms of sale
of Socomec for more information on the method for disposing of this
product.
COUNTIS ECi complies with the following European directives:
- Electromagnetic Compatibility Directive, no. 2004/108/EC (2004/12/15)
- Low Voltage Directive, no. 2006/95/EC (2006/12/12)
Compliant with RoHS directive.
Device fully protected with double insulation.
AC voltage 110 400 Vac +/-10%, 45/65Hz, 5VA
DC voltage 120 300 Vdc +/-10%, 5VA
Ambient temperature -10 55 °C IEC 60068-2-1/ -2-2
Storage temperature -20 70 °C IEC 60068-2-1/ -2-2
Ambient humidity 95 %RH IEC 60068-2-30
Vibration 2 G IEC 60068-2-6 10 to 100Hz
Dimensions 73x90x67
L x W x H
Protection index of enclosure IP51/IP20 Front/Case
Cat. Install. /degree of pollution III/2 IEC 61010-1 ed. 3 (300Vac Ph/N)
Display 1 Sec
RS 485 communication 0,5 Sec
Direct voltage 10 30 Vdc Terminal 50 reference
Current 2 15 mA According to IEC 62053-31 Class B
Line length 1000 m Min. section 1.5mm² (#16AWG)
Pulse duration 30 ms max. 16Hz
Power consumption per input 0,4 VA
Voltage 10 15 Vdc (Max. 35mA)
Current 25 mA
Accuracy 0.5 % % full scale
Input resistance 200 Ω
Power consumption per input 0,1 VA
DC breaking 30Vdc/1A
Number of equipment 32 2 shielded wires + half duplex
Case
1 contact (NO, NC)
5
RS485 bus communication (JBUS/MODBUS protocol)
Auxiliary power supply
Climate
Updating period
Vibration
Electrical safety
Digital inputs
Internal digital input polarisation power supply
Analogue inputs
Relay output