MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC
6.2 UPS connection
Remove terminal board protection.
Connect the protective earth (PE) cable.
WARNING!
Strictly observe:
- the polarity of each individual string (refer to the figure below);
- the cable cross section (refer to 'Electrical requirements' chapter).
WARNING!
Cabling errors with inversion between phase and neutral conductors may cause permanent damage to
the equipment.
Reassemble terminal board protection.
UPS In/Out
phase
Battery
type
Details
1
kVA
10-15-20 3/1 Internal
battery
INPUT
L1 L2 L3
N
AUX
L1
N
OUTPUT
L1
N
3/3
Common
inputs
INPUT
L1 L2 L3
N
OUTPUT
L1 L2 L3
N
3/3
Separated
inputs
INPUT
L1 L2 L3
N
AUX
L1 L2 L3
N
OUTPUT
L1 L2 L3
N
Refer to 'Standard
features and option'
chapter.
30-40 3/3
Separated
inputs
INPUT
L1 L2
L3
N
AUX
L1 L2
L3
N
OUTPUT
L1 L2
L3
N
1. For further details refer to 'Electrical requirements' chapter.