MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC
9.3 Bypass operations
Switching onto maintenance bypass
This operation creates a direct connection between the UPS input and output, excluding the equipment control part. This
operation is performed in the event of:
- standard maintenance.
- serious failure has occurred.
WARNING! LOAD POWERED BY AUXILIARY MAINS: your load is exposed to mains disturbances.
Enter MAIN MENU > CONTROLS > PROCEDURES.
Select MAINT. BYPASS PROC. and press ENTER.
Carry out the operations indicated on the display.
NOTE!
When an external manual bypass is present:
- carry out the procedure described above;
- close the external switch.
Switching on from maintenance bypass
Wait for the display to switch on.
Enter MAIN MENU > CONTROLS > PROCEDURES.
NOTE: In parallel configuration the procedure must be performed from the system menu.
Select START PROCEDURE and press ENTER.
Carry out the operations indicated on the display.
NOTE!
When an external maintenance bypass
(1)
is present, put the switch to position 0 (OFF).
1. Not monitored by the UPS or by the parallel system.