55EN
MASTERYS BC+ 10-40 kVA - IOMMASBCXX0G-EN 02 - SOCOMEC
15. TECHNICAL SPECIFICATIONS
Models
MASTERYS BC+
10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Input/Output phases kVA 3/1 and 3/3 3/3
Electrical specifications - Input
3/1 - Mains voltage Vin
3ph + N 400 Vac (-15/+15%) up to
-40% @ 70% of nominal load
3/3 - Mains voltage Vin 3ph + N 400 Vac (-15/+20%) up to -40% @ 70% of nominal load
Input frequency Hz 50-60 ±10%
Input power factor ≥ 0.99
Current distortion (THDi)
≤ 4% ≤ 3.5% ≤ 2%
(@: Pn, Resistive load, Mains THDv ≤ 1%)
Electrical specifications - Output
Output voltage V
1Ph+N 220/230/240 V ±1%
3Ph+N 380/400/415 V ±1%
(1)
3Ph+N 380/400/415 V
±1%
(1)
Output frequency Hz 50-60 Hz (selectable) ±0.01%
Nominal apparent power kVA 10 15 20 30 40
Nominal active power kW 9 13,5 18 27 36
Overload
(@ 25 °C; Vin > 380)
(2)
10 minutes
kW
11.25 16.875 22.5 33.75 45
1 minute 13.5 20.25 27 40.5 54
Crest factor ≥ 2.7
Voltage distortion (THDv)
≤ 1% (@: Pn, Resistive load)
≤ 5% (@: Sn, non-linear load)
Electrical specifications - Bypass
Bypass input voltage V Nominal output voltage ±15% (±20% if GENSET is used)
Bypass input frequency Hz 50-60 ±2% selectable (±8% if GENSET is used)
Environment
Operating temperature °C 0-40
(6)
(15-25 recommended)
Storage temperature °C -5 to 50
Relative humidity % up to 95% (condensation-free)
Max. altitude m 1000 (without derating)
Acoustic noise (@ 70% Pn) dBA < 43 < 49
Cooling type Air cooling
Required cooling capacity m
3
/h 240 360
Dissipated power max at Pn
nominal condition
W 450 700 950 1500 2100
kcal/h 387 602 817 1290 1806
BTU/h 1535 2388 3241 5118 7165
Dissipated power max at Pn
worst condition
W 550 800 1100 1600 2500
kcal/h 473 688 946 1376 2150
BTU/h 1877 2730 3753 5459 8530
Standards
Safety EN/IEC 62040-1, AS 62040-1
Type and performance EN/IEC 62040-3, AS 62040-3
EMC EN/IEC 62040-2
(5)
, AS 62040-2
(5)
Product certification CE - IECEE CB Scheme
Product marks RCM - EAC - CMIM
Protective class Protective Class I
Touch current < 1 mA
Protection level IP20; IP21 (option)