36 EN
MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
7.9 UPS CLOCK table, starting from 0x00CB
To send a command bit, write from the 0x00CB to 0x00CE address using as a 'Function' the code '0x10'.
See 'Functions used' and 'Summary of frame format' paragraphs for Modbus frame description.
Generic
address
Acronym Description
Value
Comments
MSB LSB
0x00CB K000 Minutes & Seconds Minute: 0 - 59 Seconds: 0 - 59 read / write
0x00CC K001 Day & hours Day: 1 - 31 Hours: 0-23 read / write
0x00CD K002 Month & day of the week Month: 1 - 12
1 = Monday - 7 =
Sunday
read / write
0x00CE K003 Year year = value + 2000 read / write