8.13 UPS clock table, starting from 0x00CB
To send a command bit time update frame, write the addresses 0x00CB to 0x00CE unsing as a 'Function' the code
'0x10'.
See 'Functions used' and 'Summary of frame format' paragraphs for Modbus frame description.
Generic
address
Acronym Description
Value
Remarks
MSB LSB
0x00CB K000 Minutes & Seconds Minute: 0 - 59 Seconds: 0 - 59 read / write
0x00CC K001 Day & hours Day: 1 - 31 Hours: 0-23 read / write
0x00CD K002 Month & day of the week Month: 1 - 12
1 = Monday - 7 =
Sunday
read / write
0x00CE K003 Year year = value + 2000 read / write