56 EN
MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
11. APPENDIX 2: MODBUS TCP IDA SPECIFICATION
The frames below are only examples:
REQUEST FROM MASTER MODBUS TCP
Original frame: 01 03 1034 0003 40C5
Encapsulated frame: 0046 0000 0006 01 03 1034 0003
where:
0046 corresponds to the transaction number
0000 corresponds to the protocol identifier
0006 corresponds to the number of bytes (length of the message)
Note: the CRC is removed in the encapsulated MODBUS frame.
REPLY FROM THE UPS MODBUS TCP:
Original frame: 01 03 06 0002 0184 0000 1960
Encapsulated frame: 0046 0000 0009 01 03 06 0002 0184 0000
where:
0046 corresponds to the transaction number
0000 corresponds to the protocol identifier
0006 corresponds to the number of bytes (length of the message)
Note: the CRC is removed in the encapsulated MODBUS frame.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec Masterys BC+ Series and is the answer not in the manual?

socomec Masterys BC+ Series Specifications

General IconGeneral
Frequency50/60 Hz
EfficiencyUp to 96%
Humidity0-95% non-condensing
Protection DegreeIP20
TopologyDouble conversion on-line
Input Voltage400 V
Output Voltage400 V
Battery TypeVRLA
CommunicationRS232, USB, SNMP
Operating Temperature0-40 °C
Output Voltage Range+/- 1%