13
TECHNICAL SPECIFICATIONS
Electrical specications - Input
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Voltage 160 (selecting wide mode) - 276 V (230 V nominal)
Frequency 50/60 Hz with automatic selection
Mains connection IEC320 (10 A) IEC320 (10 A) IEC320 (10 A) IEC320 (16 A)
Spike protection IEC 61000-4-5 300 V, 230 j / 6500 A 300 V, 460 j / 6500 A 300 V, 460 j / 6500 A 300 V, 460 j / 6500 A
Electrical specications - Output
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Voltage (in Normal Mode with AVR) The AVR increases (boost 1) the output voltage by 15%
when the input voltage drops below 90% of the nominal value.
The AVR decreases (bucks) the output voltage by 12%
when the input voltage rises above 110% of the nominal value.
Voltage (in Battery Mode) 230 V ± 5% (-10% after battery low)
Frequency 50/60 Hz
Wave form Sinusoidal
Transfer time 2-4 milliseconds (typical)
Normal Mode protections overload (110% for 3 minutes); shortcircuit protected
Battery Mode protections overload (110% for 30 seconds); shortcircuit protected
Load connection socket IEC 320 6 (10 A) 6 (10 A) 6 (10 A) 8 (10 A) + 1 (16 A)
Models
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Power (VA) 1000 1500 2000 3000
Power (W) 700 1000 1340 2100
Mechanical characteristics
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Dimensions (WxDxH mm) 87 x 385 x 235 2 x (87x 415 x 220) 2 x (87x 415 x 220) 87 x 585 x 440
Dimensions (WxDxH mm) 2U, RM - 435 x 415 x 87 435 x 415 x 87 440 x 585 x 87
Net weight (kg) 9.6 18 19 31.5
Communication
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Communication interface RS232 RS232 - USB RS232 - USB RS232 - USB
Ethernet adapter NET-VISION (TCP/IP & SNMP) optional card (not for 1000 VA model)
Local communication software UPS Management software – Windows™ & Linux (free download)
Local and remote communication software Optional UNI VISION PRO CD Windows™, AIX4.3/5.1, HP-UX10.20/11, Solaris 8/9, GNU/Linux, Novell.5/6
Data line protection NTP data line suppressor: RJ45 10 Base T
Environment
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Noise level (normal mode) < 45 dBA (at 1 meter)
Temperature 0÷40 °C (10÷25 °C for optimum battery life)
Environment Altitude: 2000 m, humidity: 95% non-condensing
Reference standards (EN) IEC62040-1-1 (safety), EN 62040-1-2 (EMC), EN 61000-4-5/C62.41:1991 (surge)
Battery
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Typical back-up time (selecting wide mode) 8 min 8 min 8 min 8 min
Battery recharge 4 hours 80% Cn (after full discharge).
Under permanent charge even when the UPS is o (mains present).