CONFIGURATION AND START-UP
9
9.1 CONFIGURATION OF THE OUTPUT VOLTAGE/BATTERY EXPANSION UNITS.
WARNING!
The factory default conguration for the Netys PR model is for operation with an output voltage
of 230 V, without any additional battery expansion units.
No conguration is required for normal use with standard back-up.
Parameter settings are congured by using free UPS communication software that can be downloaded from
www.socomec.com. If wide range has been congured the yellow LED will come ashing.
Parameter settings:
Input mode: 184÷276 V (normal); 160÷276 V (wide range);•
Output voltage: 220/230/240 V;•
Battery expansion units: 0-1-2.•
9.2 CONFIGURATION FROM MIMIC PANEL.
Output Voltage and Battery Expansion parameters are also settable by mimic panel following the below procedure.
9.2.1 Output voltage conguration menu.
Press • button for 3 seconds to start the procedure: rst current set-
ting (230 V) LED ashing;
Push • button again: second current setting (240 V) LED ashing;
Push • button again: third current setting (220 V) LED ashing;
Press • button for 3 seconds to conrm, at the same time, change to
Battery extentions conguration menu.
9.2.2 Battery expansion conguration menu (after Output Voltage conguration).
Push • button: rst conguration; 0 expansion (only UPS) LED ash-
ing;
Push • button: second conguration; 1 expansion LED ashing;
Push • button: third conguration; 2 expansion LED ashing;
Press • button for 3 seconds to conrm conguration and exit.
240 V
230 V
220 V
2 battery expansion
1 battery expansion
0 (no battery expansion)