SAFETY STANDARDS
The UPS generates a leakage current of about 1.5 mA. To guarantee the maximum limit leakage current of 3.5 mA, •
make sure that the maximum leakage current of the load is 2 mA. If the load current exceeds this value, have
qualied personnel connect the UPS to an industrial type, IEC 309 compliant power supply mains, with a current
of correct dimensions for the UPS power rating.
Netys UPS is intended for commercial and industrial use; it is not recommended for use in medical applications •
that are essential to the survival of the patient.
Use the UPS in accordance with the technical specications given in the User Manual.•