4. CONNECTIONS
4.1. Cable or bar connections
Recommended tightening torque:
M12: 40 N.m
Maximum tightening torque:
M12: 45 N.m
4.1.1. Power connection terminals
1250A 1600A 2000A 2500A 3200A
Minimum bars
section Cu (mm
2
), Ith
2x80
x5
2x100
x5
3x100
x5
4x100
x5
3x100
x10
Maximum cables
section Cu (mm
2
)
4x185 6x185 - - -
Maximum bars width
Cu (mm)
63 100 100 100 100
5. TROUBLE SHOOTING GUIDE
It is not possible to
manually operate the
switch
Make sure that the product is not padlocked
Verify the rotation direction of the handle
Apply a sufcient progressive action in the direction as indicated on the
handle
Impossible to padlock Verify that the SIDER is in 0 position
(Padlocking is only possible in 0 position for standard products)