11
EN
SIDER - 546418A - SOCOMEC
4. CONNECTIONS
4.1. Cable or bar connections
Recommended tightening torque:
• M12: 40 N.m
Maximum tightening torque:
• M12: 45 N.m
4.1.1. Power connection terminals
1250A 1600A 2000A 2500A 3200A
Minimum bars
section Cu (mm
2
), Ith
2x80
x5
2x100
x5
3x100
x5
4x100
x5
3x100
x10
Maximum cables
section Cu (mm
2
)
4x185 6x185 - - -
Maximum bars width
Cu (mm)
63 100 100 100 100
5. TROUBLE SHOOTING GUIDE
It is not possible to
manually operate the
switch
• Make sure that the product is not padlocked
• Verify the rotation direction of the handle
• Apply a sufcient progressive action in the direction as indicated on the
handle
Impossible to padlock • Verify that the SIDER is in 0 position
(Padlocking is only possible in 0 position for standard products)