EasyManua.ls Logo

Sofar solar 20KTLX-G3 - Page 32

Sofar solar 20KTLX-G3
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SOFAR 15~24KTLX-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 28 -
Ban multiple Inverters use one circuit breaker
Ban connect loads between inverter and circuit breaker
Caution
Must use five core outdoor cable, the recommend AC cable and Residual current
breaker (RCB) as below table 5-1:
Model
Cross section
area of Cu cable
mm
2
Muti-core
outdoor cable
mm
AC Circuit Breaker
specification
SOFAR
15KTLX-G3
6~12
recommend 10
18~25
40A/230V/3P current
leakage protection 0.1A
SOFAR
17KTLX-G3
6~12
recommend 10
18~25
40A/230V/3P current
leakage protection 0.1A
SOFAR
20KTLX-G3
6~12
recommend 10
18~25
50A/230V/3P current
leakage protection 0.1A
SOFAR
22KTLX-G3
7~14
recommend 12
18~25
63A/230V/3P current
leakage protection 0.1A
SOFAR
24KTLX-G3
7~14
recommend 12
18~25
63A/230V/3P current
leakage protection 0.1A
Table 5-1 The recommend AC cable and Residual current breaker (RCB)
The inverter does not require an external residual-current device when in
operation.
If one is required under local regulations, SOFAR recommends a type A or B RCD
with sensitivity of 100mA or higher.
Where local electricity code requires an RCD with a lower leakage ratings, the
discharge current might result in nuisance tripping of the external RCD. Sofar
recommends the following measure in selecting an external RCD to avoid nuisance
tripping:
1: Selecting appropriate RCD.
2: Configure the trip current of inverter internal RCD to a lower value that the trip
current of the external RCD.

Related product manuals