To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SOFAR 3K~6KTLM-G3 User manual
Copyright © Shenzhen SOFAR SOLAR Co., Ltd
- 46 -
(F>)
value
Trip delay
time
-
-
-
-
Maximum
disconnection
time
0.2s
0.2s
0.2s
0.2s
Default volt-watt settings for different regions are shown in the following table:
Region
Default value
V
L2
V
L1
V
W1
V
W2
Australia A
Voltage
207
215
253
260
Inverter output (P) % of S
rated
20%
100%
100%
20%
Australia B
Voltage
195
215
250
260
Inverter output (P) % of S
rated
0%
100%
100%
20%
Australia C
Voltage
207
215
253
260
Inverter output (P) % of S
rated
20%
100%
100%
20%
Default volt-var settings for different regions are shown in the following table:
Region
Default value
V
V1
V
V2
V
V3
V
V4
Australia A
Voltage
207
220
240
258
Inverter reactive output
(Q) % of S
rated
44% supplying
0%
0%
60% sinking
Australia B
Voltage
205
220
235
255
Inverter reactive output
(Q) % of S
rated
30% supplying
0%
0%
40% sinking
Australia C
Voltage
215
230
240
255
Inverter reactive output
(Q) % of S
rated
44% supplying
0%
0%
60% sinking
5. On-Off Control
Inverter on-off local control.
6. Set Energy
Set the total power generation. You can modify/clear the total power generation
through this option.