80-136KTL User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 34 -
Note
Before connect to grid, please ensure the grid voltage and frequency of local
grid meet the requirement of inverter , any question please seek local grid
company for help.
Inverter can only connect to grid after get the permission from local grid
company
Should not connect any loads between inverter and AC circuit breaker
OT/DT Requirement
When use copper core cable, please use copper terminal connector
When use copper clad aluminum cable, please use copper terminal connector
When use aluminum core cable, please use Copper and aluminum transition
terminal connector or aluminum terminal connector
AC terminal block
AC terminal block
AC terminal block
AC terminal
Cu cable
terminal
Cu cable
terminal
Al cable
terminal
Cu-Al
transition
terminal
Cu core
cable
Al core
cable
Al core cable
Cu- Al
cable

Related product manuals