Figure 5-6 OT/DT Requirement for terminal connection
Figure 5-7 AC Terminal size
5.4.4 Wring Procedure
The section will use a five core wire as a sample, four core wire has same
connection process
Figure 5-1 Recommend AC cable size
Name
Type
Area(mm²)
AC Cables
RecommendedOutdoor
four-core/five-core copper or
aluminum wire
Copper Wire95~185Aluminum
Wire120~240
PE Wirereference 5.3
STEP 1Open the cover, refers to section 5.3.1
STEP 2Turn OFF the AC circuit breaker and secure against reconnection
STEP 3Unscrew the nut of the AC terminal block and select the sealing ring
according to the outer diameter of the cable. Insert the nut, sealing ring into the
cable in sequence.