TROUBLESHOOTING HANDLING
114 HYD 5K...20KTL-3PH
ID030
ConsistentFault_Vgrid
The line voltage
sample between
the master DSP
and the slave DSP
is not consistent.
ID033
SpiCommFault(DC)
SPI communication
error (DC)
ID034
SpiCommFault(AC)
SPI communication
error (AC)
ID035
SChip_Fault
Chip error (DC)
ID036
MChip_Fault
Master chip error
(AC)
ID037
HwAuxPowerFault
Auxiliary voltage
error
ID041
RelayFail
Relay detection
failure
ID042
IsoFault
Insulation
resistance is too
low
Check the insulation
resistance between the
PV generator and earth
(ground), rectify the fault
if there is a short circuit.
ID043
PEConnectFault
Earth fault
Check the PE conductor
for function
ID044
PV Config Error
Incorrect input
mode configuration
Check the MPPT input
mode setting (parallel
mode/independent mode)
of the inverter and correct
if necessary.
ID045
CTD isconnect
CT error
Check that the wiring of
the current transformer is
correct.