TROUBLESHOOTING HANDLING
HYD 5K...20KTL-3PH 123
ID173
FanFault5
Fan 5 fault
ID174
FanFault6
Fan 6 fault
ID175
FanFault7
Fan 7 fault
ID176
MeterCommLose
Communication
fault with meter
unit
Check communication to
meter
ID177
BMS OVP
BMS overvoltage
alarm
Internal error in the
connected lithium battery.
Switch off the inverter
and the lithium battery,
wait 5 minutes and then
switch the components on
again.
If the error persists,
contact technical support.
ID178
BMS UVP
BMS Undervoltage
alarm
ID179
BMS OTP
BMS High
temperature
warning
ID180
BMS UTP
BMS low
temperature
warning
ID181
BMS OCP
BMS overload
warning during
charging and
discharging
ID182
BMS Short
BMS Short circuit
alarm