ELECTRICAL CONNECTIONS
40 HYD 5K...20KTL-3PH
ATTENTION
Qualification
The installation and maintenance of the inverter must be
carried out by an electrician.
NOTE
The open-circuit voltage of the modules connected in
series must be lower than or equal to 1000 V.
The connected PV modules must be compliant with IEC 61730 class
A.
Model
Isc PV (absolute
maximum)
Maximum output
overvoltage
protection
HYD 5KTL-3PH
15 A/15 A
8 A*3
HYD 6KTL-3PH
10 A*3
HYD 8KTL-3PH
13 A*3
HYD 10KTL-3PH
30 A/30 A
16 A*3
HYD 10KTL-3PH-A*
16 A*3
HYD 15KTL-3PH
24 A*3
HYD 20KTL-3PH
32 A*3
The DVC (decisive voltage classification) is the circuit voltage which
constantly occurs between two arbitrary live parts during proper use
in a worst-case scenario: