TROUBLESHOOTING HANDLING
SOFAR 1100...3300TL-G3 75
The sample value of the
DCI between the master
DSP and the slave DSP is
not consistent
The sample value of the
GFCI between the master
DSP and the slave DSP is
not consistent
The SPI communication
between the master DSP
and the slave DSP is faulty
The SCI communication
between the control board
and communications
board is faulty
The insulation resistance
is too low
Check the insulation resistance
between the PV generator and
earth (ground), and rectify the error
in the event of short-circuiting.
The temperature of the
inverter is too high
Ensure that the mounting position
and method both comply with the
necessary requirements.
Check whether the ambient
temperature at the installation
location exceeds the upper limit
value. If so, improve the ventilation
in order to reduce the temperature.
The DC/DC booster
temperature is too high
The ambient temperature
is too high