5.3. Connect grid side of inverter(AC-Output)
SOFAR 60~80KTLX-G3 connect to utility grid by using AC power cable. The AC
connection must meet the requirement of local grid operator.
Ban multiple Inverters use one circuit breaker
Ban connect loads between inverter and circuit breaker
Caution
Must use five core outdoor cable, the recommend AC cable and Residual current
breaker (RCB) as below table 5-1:
Item
Model
L/N Cross
section area
of Cu or Al
cable
mm2
PE Cross
section area
of Cu or Al
cable
mm2
Muti-core
outdoor cable
diameter
mm
AC Circuit
Breaker
specification
SOFAR
60KTLX-G3
50~70
16~25
≤28
120A/380V/3P
IN=0.3A
SOFAR
80KTLX-G3
70~95
16~25
≤28
150A/380V/3P
IN=0.3A
*SOFAR
70KTLX-G3
70~95
16~25
≤28
150A/380V/3P
IN=0.3A