SOFAR 60-80KTLX-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
Leakage current
consistency error
Grid voltage
consistency error
SPI communication
error (DC)
SPI communication
error (AC)
Internal faults of inverter, switch OFF inverter,
wait for 5 minutes, then switch ON inverter.
Check whether the problem is solved.
If not, please contact SOFARSOLAR technical
support.
Check the insulation resistance between the
photovoltaic array and ground (ground), if there is
a short circuit, the fault should be repaired in
time. If not solved, please contact
SOFARSOLAR technical support.
Check ac output PE wire for grounding. If not
solved, please contact SOFARSOLAR technical
support.
Check the input mode (parallel/independent
mode) Settings for the inverter. If not solved,
please contact SOFARSOLAR technical support.
Please check the wiring of input, output and
communication according to the user's manual. If
the use method is not ruled out, please contact
SOFARSOLAR technical support..
Input reverse
connection error
It is internal fault of inverter.
Radiator 1
temperature
protection
Ensure the installation position and installation
method meet the requirements of this user
manual. Check whether the ambient temperature
of the installation position exceeds the upper
limit. If yes, improve ventilation to decrease the
temperature. Check whether the inverter has dust
and dust, whether there are foreign matters