SOFAR 60-80KTLX-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
55
parallel
ID088
IacUnbalance
Unbalanced output
current
ID097
HwLLCBusO
VP
LLC hardware
overvoltage
ID098
HwBusOVP
Inverter bus
hardware
overvoltage
ID099
HwBuckBoos
tOCP
BuckBoosthardware
overflows
ID100
Reserved
Reserved
ID102
HwPVOCP
PV hardware
overflows
ID103
HwACOCP
Ac output hardware
overflows
ID105
MeterCommF
ault
Meters
communication
fault
Internal faults of inverter, switch OFF inverter,
wait for 5 minutes, then switch ON inverter.
Check whether the problem is solved.
If not, please contact SOFARSOLAR technical
support.
ID106
SNMachineF
ault
Serial number
model error
ID110
Overload1
Reserved
ID111
Overload2
Reserved
ID112
Overload3
Reserved
ID113
OverTempDe
rating
Overtemperature
derating
Ensure the installation position and installation
method meet the requirements of this user
manual. Check whether the ambient temperature
of the installation position exceeds the upper
limit. If yes, improve ventilation to decrease the
temperature. Check whether the inverter has dust
and dust, whether there are foreign matters
blocking the fan at the air inlet. If so, please
improve the ventilation and heat dissipation of the
environment. It is recommended that the inverter
should be cleaned once every half year or one
year.
ID114
FreqDerating
Frequency derating
If it occurs frequently, please check whether the
grid voltage and grid frequency are within the
allowable range of the inverter; if not, please
contact the customer service of SOFARSOLAR;
if yes, please check whether the connection
between the circuit breaker at the AC side and the
output cable is normal; if the grid voltage and grid
frequency are within the allowable range of the
inverter, and the AC side wiring is confirmed to
be correct, the alarm still appears frequently With
the approval of the local power operator, please
ID115
FreqLoading
Frequency loading
ID116
VoltDerating
Voltage derating
ID117
VoltLoading
Volatge loading
ID121
SpdFail(DC)
Lightning
protection
fault(DC)