Inline Energy Meter
Quick Installation Guide
For Europe, APAC and South Africa
B
solaredge.com
Werner-Eckert-Strasse 6/81829
Munich/GermanySolarEdge
Technologies Gmbh
Subject to change withoutnotice.
© SolarEdge Technologies, Ltd.
All rights reserved. August 2021.
Usage Options
Mounting and Wiring
Box Contents
One (1) Energy meter
One (1) Quick Installation Guide
One (1) RS485 Terminal block
1
3
4
Default Communication
Metal Enclosure or Extended Range
Datasheet
See section C on back page for optional Modbus communication
Scan for SolarEdge
Energy Net plug-in kits
to use with the inverter
SolarEdge Energy Net
Complete Installation guide
Scan for SolarEdge Energy
Net plug-in installation guide
WARNING! HAZARD OF
ELECTRIC SHOCK DISCONNECT
POWER BEFORE SERVICE OR
INSTALLATION
NL3L2L1
Cross-section: 1.5 25 mm
2
/ 15 - 3 AWG
L1
L2
L3
N
3Ø Meter Wiring - Accuracy class A (2%)
NL3L2L1
N
L3
L2
L1
Cross-section: 1.5 25 mm
2
/ 15 - 3 AWG
OFF
3Ø Meter Wiring - Accuracy class B (1%)
CAUTION! DO NOT use circuit
breaker with a rated current of
more than 65A
N
L
Cross-section: 1.5 25
mm
2
/ 15 - 3 AWG
230/400 VAC Wye
Grid (max. 65A)
1Ø Meter Wiring - Accuracy class B (1%)
CAUTION! DO
NOT use circuit
breaker with a
rated current of
more than 65A
N
L
1.2Nm
1.2Nm
Connect to L3 when using this meter in 1Ø grid
Connect to L3 when using this meter in 1Ø grid
1.2Nm
RS485 Defaults:
Termination = ON
ID = 2
1
2
3
4
3X 230/400 VAC Wye Grid
(max. 65A per each phase)
3X 230/400 VAC Wye Grid
(max. 65A per each phase)
1.1Nm
2
Scan for External Energy Net
antenna installation guide
1Ø Meter Wiring - Accuracy class A (2%)
N
L
N
L
Cross-section: 1.5
25 mm
2
/ 15 - 3 AWG
CAUTION! DO
NOT use circuit
breaker with a
rated current of
more than 65A
230/400 VAC Wye
Grid (max. 65A)
1.2Nm
DE FR HU IT
NL PL SP SWE
Question and Answer IconNeed help?

Do you have a question about the SolarEdge MTR-240-3PC1-D-A-MW and is the answer not in the manual?

SolarEdge MTR-240-3PC1-D-A-MW Specifications

General IconGeneral
ModelMTR-240-3PC1-D-A-MW
CategoryMeasuring Instruments
Voltage Rating240 V
Frequency50/60 Hz
Humidity0-95% non-condensing
Phase3-Phase
CommunicationModbus
CertificationsANSI C12.20
Operating Temperature-40°C to +70°C

Summary

Usage Options

Default Communication

Details on the default communication settings for the energy meter.

Metal Enclosure or Extended Range

Information regarding the use of metal enclosures or extended range options.

Mounting and Wiring

1 Meter Wiring - Accuracy class A (2%)

Wiring diagram for a single-phase meter with accuracy class A (2%).

1 Meter Wiring - Accuracy class B (1%)

Wiring diagram for a single-phase meter with accuracy class B (1%).

3 Meter Wiring - Accuracy class B (1%)

Wiring diagram for a three-phase meter with accuracy class B (1%).

3 Meter Wiring - Accuracy class A (2%)

Wiring diagram for a three-phase meter with accuracy class A (2%).

Optional Modbus Connection

RS485 Wiring

Instructions for connecting the meter using RS485 wiring for Modbus.

Setting the Inverter DIP Switches

Guidance on configuring inverter DIP switches for Modbus communication.

Connecting and Managing the Meter Using the SetApp Application

For RS485

Steps for connecting and managing the meter via SetApp for RS485.

For Energy Net

Steps for connecting and managing the meter via SetApp for Energy Net.

Keys, LED Indications and Screen Navigation

Communication Status

Explanation of LED indications for communication status.

Related product manuals