6.3.6 Settings
This menu can be used to set different communication parameters and monitoring func-
tions. All settings can also be implemented with MaxTalk.
Parameter Description
Language Selection of the display language (German, English, French, Italian, or Spanish).
The display language can be selected independently of the selected specic
country settings.
Time Setting the internal clock
Date Setting the displayed date
Device address Denition of the device address between 1 and 249. If you connect several
inverters and accessory components to become one MaxComm communication
network, each device within the network must have an individual address.
IP
Conguration of the Ethernet interface. Details see 7.1 “Conguration of the data
communication interfaces”; page 97.
Netmask
TCP Port
Status relay delay Setting the switching delay of the status signalling contact
Pinst tot Rated output of the PV generator (entry only possible in MaxTalk).
Status relay
The functions of the status relay or the status signalling contact can be adjusted. There
are four different functional settings.
Setting Description
Off The status signalling contact is always open.
Mains When the inverter starts mains operation, the status signalling contact closes
immediately and remains closed as long as the inverter is feeding in. If the inverter
is no longer feeding into the grid, the status signalling contact opens after the
adjustable delay time has expired.
Error If a warning, failure, or device error occurs with the inverter, the status signalling
contact closes after the adjustable delay time has expired (the events are listed
in 10.2 “Diagnosis & measures”; page 102). The status signalling contact opens
immediately when the error is no longer present.
On This setting is designed for controlling an external motorised AC disconnector, for
example. When the inverter is switched on (sufciently high DC input voltage), the
status signalling contact closes. The status signalling contact will only re-open
when the inverter is switched off (DC input voltage too low).