106
Operation on LCD
divided equally as above and it is unrelated with the loads connected with each
phase.
Three phase
inverter
5 kW
5 kW
5 kW
Load 1
4 kW
Load 2
5 kW
Load 3
6 kW
Meter
Setting EPS Setting
Select and enter EPS Setting interface and set Frequency, Min SOC and Min ESC SOC.
Frequency: Default: 50Hz. Output frequency of EPS
Min SOC: Default: 10%, range: 10%-100%
»
If the battery SOC is lower than the Min SOC of the inverter, The inverter
displays BatPowerLow. If PV is not available at this time, the inverter will shut
down.
Min ESC SOC: Default: 30%, range: 15%-100%
»
In EPS mode, after reporting a BatPowerLow, the minimum SOC required to
re-enter EPS mode is determined. If the PV charge the battery and bring the
battery level up to the Min ESC SOC, the inverter will automatically switch
back to EPS mode.
=====EPS Setting=====
>Frequency
50Hz/60Hz
=====EPS Setting=====
>Min SoC
10%
=====EPS Setting=====
>Min ESC SoC
30%
To enable the Super-Backup mode and allow only PV without battery to enter
EPS. Disable is the default setting.
=====EPS Setting====
Super-Backup
> Disable <
For three-phase inverters, the output power of EPS terminals is restricted to half (50%) of
the nominal output power of EPS terminals (with battery) total phase. For more details in
the table below.
EPS output
(Without
battery)
X3-ULT-
15KP
X3-ULT-
15K
X3-ULT-
19.9K
X3-ULT-
20K
X3-ULT-
20KP
X3-ULT-
25K
X3-ULT-
30K
Normal output
power (W)
7500 7500 9999 10000 10000 12500 15000