15
Product Overview
Allowed discharging
period
The working logic remains the same as for self-use mode. The
difference is:
In the self-use mode when there is no PV input and the battery
SOC reaches Min SOC
1
(on-grid min SOC), the battery will
enter a dormant state. At this time, if the grid power is lost, the
inverter cannot switch to EPS mode.
In the backup mode, when there is no PV input and the battery
reaches Min SOC (on-grid min SOC), the inverter enters
standby. At this time, if the grid power is lost , it will switch to
EPS mode until the battery is discharged to the Min SOC
2
(off-
grid min SOC).
Note:
Min SOC
1
(on-grid min SOC): Minimum SOC under grid connection. 30% by default, the
settable range is 30%~100%.
Min SOC
2
(off-grid min SOC): Minimum SOC under off-grid conditions. 10% by default, the
settable range is 10%~100%.
NOTICE!
You can set two configurable working periods: forced charging period and allowed
discharging period in backup mode. Please refer to "Charge & Discharge Period" for
details.
NOTICE!
If there is a foreseeable power outage, it is advisable to switch to backup mode in
advance from other modes.