14
15
Technical DataTechnical Data
4. Technical Data
4.1 DC Input
4.2 AC Output
1200
450
50
360
40-450
2200
450
50
360
40-450
3000
450
50
360
40-450
4000
450
50
360
40-450
1/1
16
22
X1-MINI
-0.6K-G4
Model
I PV array Short Circuit
SC
Current [d.c.A]
Max. PV array input power [Wp]
Max. PV voltage [d.c.V]
Startup voltage [d.c.V]
Nominal input voltage [d.c.V]
MPPT voltage range [d.c.V]
No. of MPP trackers/Strings
per MPP tracker
Max. PV current [d.c.A]
5000
550
50
360
40-550
6000
550
50
360
40-550
700
3.1
1100
4.8
1500
6.5
2000
8.7
Rated output apparent power [VA]
Nominal AC output current [a.c.A]
Max. output apparent
power [VA]
Max. output continuous current
[a.c.A]
Nominal AC voltage [a.c.V]/
Grid range
Nominal grid frequency [Hz]
220/230/240; 90-290
50/60; ±5
0.8leading-0.8lagging
<3
Displacement power factor
ITHDi (rated power) [%]
Model
2500
10.9
3300
14.4
3000
13.1
1400
450
50
360
40-450
600
6600
550
50
360
40-550
2.6
600
3
770
3.5
1210
5.5
1650
7.5
2200
10
2750
12.5
3300
15
3300
15
X1-MINI
-0.7K-G4
X1-MINI
-1.1K-G4
X1-MINI
-1.5K-G4
X1-MINI
-2.0K-G4
X1-MINI
-2.5K-G4
X1-MINI
-3.0K-G4
X1-MINI
-3.3K-G4
X1-MINI
-0.6K-G4
X1-MINI
-0.7K-G4
X1-MINI
-1.1K-G4
X1-MINI
-1.5K-G4
X1-MINI
-2.0K-G4
X1-MINI
-2.5K-G4
X1-MINI
-3.0K-G4
X1-MINI
-3.3K-G4
4.3 System Data, Protection and Standard
98
96
98
97
98
97
98
97
Max. efficiency [%]
Euro. efficiency [%]
Standby consumption
[W] @Night
Over/under voltage protection YES
DC isolation protection YES
Monitoring ground fault protection YES
Grid monitoring YES
DC injection monitoring YES
Back feed current monitoring YES
Residual current detection YES
Anti-islanding protection YES
Over temperature protection YES
SPD (PV/AC) Type II (Optional)
98
97
98
97
98
96
98
97
Ingress protection
Protective class
Overvoltage category
Operating ambient temperature
range [℃]
Max. operation altitude [m]
Humidity [%]
Typical noise emission [dB]
Storage temperature [℃]
Dimensions(W×H×D) [mm]
Weight [kg]
Cooling concept
<1
I
II (DC),III (AC)
-25-60
<4000
0-100
25
-30-70
290x206x120
5.2
5.5
5.2 5.2 5.2 5.2
5.5
5.5
Nature cooling
AFCI Optional
Safety EN/IEC62109-1/2
Grid monotoring
X1-MINI
-0.6K-G4
X1-MINI
-0.7K-G4
X1-MINI
-1.1K-G4
X1-MINI
-1.5K-G4
X1-MINI
-2.0K-G4
X1-MINI
-2.5K-G4
X1-MINI
-3.0K-G4
X1-MINI
-3.3K-G4
IEC61727, EN50549, G98, AS 4777.2, VDE4105, CEI 0-21, VFR
Communication interfaces
RS485/DRM/USB/Heat Pump, Optional: CT/Meter;
Optional monitoring dongle
Pocket WiFi/LAN/4G
Max. inverter backfeed current
to the array [d.c.A]
0
Current (inrush) [a.c.A]
50
58 (15 ms)
35
Maximum output fault current [a.c.A]
Maximum output overcurrent
protection [a.c.A]
Active anti-islanding method
Frequency shift
Inverter typology
Non-isolated