Parameter Settings
30
3030
30
Press Select
Then press

keys to set the protocol:
COMM. PROTOCOL
PROFIBUS
For MODBUS parameters see page 29.
Press Select
Then press

keys to set number of input
bytes to be scanned.
Range: 2, 4, 6, …32
NO. OF IN BYTES
2
Press Select
Then press

keys to set number of outputs.
Range: 1,2.
Where:
1 indicates no control via profibus. (only monitoring)
2 indicates full control via profibus
NO. OF OUT BYTES
1
Press Select
Then press

keys to set Communication Serial Link
Number
Range: 1-127 (for up to 32 starters on one twisted pair)
SERIAL LINK NO.
127 (OFF)
Note:
Serial link number must be set to 127 (Off) if
communication is not in use.
Press Select
To store selected parameters press
Store
key
STORE ENABLE
COMM. PARAMETERS
When parameters have been correctly stored the LCD
displays:
DATA SAVED OK
This concludes
COMMUNICATION
PARAMETERS
setting.