EasyManuals Logo

SOLIS S6-EH3P5K2-H User Manual

SOLIS S6-EH3P5K2-H
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
User Manual
OV-G-V1: 304.8---332.6V
OV-G-V1-T: 1---13S
OV-G-V2: 304.8---360.3V
OV-G-V2-T: 0.12S
UN-G-V1: 14---243.9V
UN-G-V1-T: 2---50S
UN-G-V2: 14---138.6V
UN-G-V2-T: 0.16---21S
Startup-T: 10-600S
OV-G-F1: 61-66Hz
OV-G-F1-T: 180---1000S
OV-G-F2: 61.8-66Hz
OV-G-F2-T: 0.16---1000S
UN-G-F1: 50-59Hz
UN-G-F1-T: 180---1000S
UN-G-F2: 50-57Hz
UN-G-F2-T: 0.16---1000S
Restore-T: 10-600S
Table 6.2 Setting ranges for User-Def
NOTE
The initial value of the User-Def standard is for reference only. It does
not represent a correct value suitable for use.
6. Normal operation
43
NOTE
All voltages is Table 6.2 are referenced Line (L) to Neutral (N). For Line (L) to
Line (L) voltages, values need to be multiplied by
3

Table of Contents

Other manuals for SOLIS S6-EH3P5K2-H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SOLIS S6-EH3P5K2-H and is the answer not in the manual?

SOLIS S6-EH3P5K2-H Specifications

General IconGeneral
BrandSOLIS
ModelS6-EH3P5K2-H
CategoryInverter
LanguageEnglish

Related product manuals