3.4.4 Prospective short-circuit current
The meter always measures impedance. The short-circuit current is calculated according to the
following formula:
S
n
k
Z
U
I
where: U
n
nominal voltage of the network being tested selected in MENU, Z
S
impedance measured.
On the basis of U
n
nominal voltage selected (point 2.1.1), the meter automatically recognizes the
measurement at phase voltage or phase-to-phase voltage and takes it into account in the calculations.
If the voltage of the network being tested is outside the tolerance range, the meter will not be able
to determine a proper nominal voltage for the short-circuit current calculation. In such a case, horizontal
dashes will be displayed instead a short-circuit current value. The following diagram shows voltage
ranges for which short-circuit current value is calculated.
230
400
440
U [V]
207
253
360
115
127
180
200
220
220
380
418
198
242
342
373
415
440
216
240
264
103
440
U [V]
440
U [V]
U [V]
U =115V
n
U =220V
n
U =230V
n
U =240V
n
110
121
171
190
209
99
440
U [V]
U =110V
n
127
140
198
220
242
114
440
U [V]
U =127V
n
99
99
99
99
99
Voltage range for which impedance
measurement is made
U voltage ranges for which short-
circuit current value is calculated
U
L-L
voltage ranges for which short-cir-
cuit current value is calculated

Table of Contents

Other manuals for Sonel MPI-520

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sonel MPI-520 and is the answer not in the manual?

Sonel MPI-520 Specifications

General IconGeneral
BrandSonel
ModelMPI-520
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals