Operation and Maintenance Documentation GUARD v202301
1. PURPOSE OF THE DEVICE
The air curtain is intended to be used in regions with a moderate and cold climate, in spaces where the temperature ranges
from -10 to +40°C, in conditions free from external factors such as pollens and hydrometeor (horizontal precipitation).
In winter, air curtains protect against heat loss in rooms by directing an airstream across the entrance and preventing cold air
from entering the heated space. In summer, the curtains may be used as cooling devices preventing the entry of hot air and
pollutants from outside.
The GUARD air curtains are designed to protect against heat losses in buildings of medium and high capacity and with a
required mounting height of 4 m such as:
supermarkets, large retail spaces,
car showrooms and service stations,
sports and show halls,
exhibition surfaces
2. BASIC TECHNICAL PARAMETERS
TECHNICAL PARAMETERS
Curtain with water heater Curtain with electric heater Curtain without heater
GUARD 100W
GUARD 150W
GUARD 200W
GUARD 100E
GUARD 150E
GUARD 200E
GUARD 100C
GUARD 150C
GUARD 200C
Lenght of unit m 1 1.5 2 1 1.5 2 1 1.5 2
Max installation height m 4 4 4
Max air output m³/h
1200/1550/2000
2200/3000/3600
2900/4000/4800
1200/1550/2000
2200/3000/3600
2900/4000/4800
1250/1600/2100
2250/3100/3700
3000/4200/5000
Heat output * kW 10-16 20-29 25-40 4 - 7 6,5 - 11 8,5 - 14 - - -
Temperaturę increase ΔT **
ΔT - - - 12 13 14 - - -
Max working pressure MPa 1,6 - - - - - -
Diameter of connection
nozzels
˝ 1/2' - - - - - -
Motor power supply,
consumption
V/Hz A
230/50 1,45A 230/50 1,45A 230/50 2,0A 230/50 1,45A 230/50 1,45A 230/50 2,0A 230/50 1,45A 230/50 1,45A 230/50 2,0A
Motor power supply,
consumption ***
V/Hz A
220/60 1,8A 220/60 1,7A 220/60 2,2A 220/60 1,8A 220/60 1,7A 220/60 2,2A 220/60 1,8A 220/60 1,7A 220/60 2,2A
Motor power kW 0,16 0,18 0,26 0,16 0,18 0,26 0,16 0,18 0,26
Electric heater power
supply, consumption ****
V/Hz A
- - - 400/50 12,6A 400/50 19,1A 400/50 25,1A - - -
Weight with water/without
water
kg 18,0 / 16,5 22,6 / 20,5 31,0 / 28,0 17 21,5 29 15 18,5 25
Volume leveleg I / II / III dB (A) 44 / 49 / 59 45 / 49 / 61 46 / 49 / 61 44 / 49 / 59 45 / 49 / 61 46 / 49 / 61 45 / 50 / 60 46 / 50 / 61 47 / 50 /61
Protection class IP IP21 IP21 IP21
* heat output for water agent 90/70 and inlet air temperature 0°C
** temperature increase for 18°C ambient air
*** version for KSA, Egypt
**** power consumption for ambient air temperature 18°C and cable length 10m
Energy consumption [A] goes higher in relation to decrease of air inlet temperature or extension of supply cables lenght
Noise level measured in distance of 3 m in open space building
DIMENSIONS OF THE GUARD 100-150-200 W, E, C CURTAINS