30
Sookook Corporation
3C. Combustion Head Inspection and Replacement
Positioning Method of Ignition Electrode
- Do not connect the cable of the ignition electrode and flame rod interchangeably.
- Keep the electrode well in the center to prevent metal parts from touching.
- Electric arc discharge shall be generated between high voltage electrode and ground electrode core.
Note
1- high voltage electrode
2- flame rod
3- ground electrode core
[Figure 2F-A. BX-TYPE HEAD]
Note
1- high voltage electrode
2- flame rod
3- Diffuser
[Figure 2F-B. LX-TYPE HEAD]
3
1
2
1.5~2mm
3
2
1
1.5~2 mm
1.5~2mm
5~8mm